23
FIGURE 16
ACCEL/DECEL "2" CONENCTIONS
TABLE 10
ACCEL/DECEL "2" PROGRAMMING
Function No. Code/Range
7.05: Multi-Function Input Terminal 6 0005: Accel/Decel 2
7.16: Accel/Decel 2 Time 0.3 180.0: Set to Desired Time*
*Factory set to 1.5 seconds.
4.4 FORWARD/STOP-REVERSE/STOP
Remote Forward/Stop and Reverse/Stop operation can be performed by
connecting switches or contacts to the Multi-Function Input Terminals. See
Figure 17, on page 24, for connections. See Table 11, on page 24, for drive
programming.
Connect the Start/Stop Switch or Contact to Multi-Function Input Terminal "5",
which is factory set for N.O. Start ("0010"). Connect the Forward/Stop and
Reverse/Stop Switches or Contacts to any Multi-Function Input Terminals
"1" – "7". Terminals "3" and "4" have been arbitrarily chosen for Forward/Stop
and Reverse Stop. Connect the common of the switches or contacts to any
available common terminal ("8", "12", "14", "16", "18", "20", "22").
Operation: When the Forward/Stop Switch or Contact is closed, the drive will run
in the forward direction. When the Forward/Stop Switch or Contact is opened,
the drive will stop. When the Reverse/Stop Switch or Contact is closed, the drive
will run in the reverse direction. When the Reverse/Stop Switch or Contact is
opened, the drive will stop.